1 General
1.0.1 in order to carry out "precaution is given priority to, combine prevention with elimination of the" work principle of fire prevention and control, protection of song and dance entertainment places of fire safety, preventing and reducing fire hazard, combine this province actual situation, establish this standard.
1.0.2 This standard is applicable to the construction area 50m
2 and 50m2 over the following indoor places:
In 1, Cara OK hall ballroom, nightclubs and other entertainment places;
2 with entertainment features music cafes, bars and catering establishments;
3 Internet cafes, entertainment, office of electronic entertainment and amusement places;
4 sauna, massage and other places.
1.0.3 amusement venues fire design should be in accordance with the provisions of this standard, be in compliance with current national fire laws, administrative regulations and technical standards.
2 of the total plane layout and layout
2.0.1 song and dance entertainment general plane layout should be consistent with the requirements of city planning, to meet the fire code on fire protection spacing, fire fighting, fire lanes and fire water environment regulation.
2.0.2 song and dance entertainment should be set up in the one or two stage the fire resistance rating of buildings.
2.0.3 song and dance entertainment should be set in the building within the first layer, the two layer or the three layer on the external walls of parts. When must be set in the construction of the other floors, there should be in line with the following provisions:
1 should not be set in the underground two layer and two layers of the following. When set in the ground floor, underground layer of the ground and the outdoor entrance floor height difference should not be greater than 10m;
In 2 a hall, room area of the building shall be not more than 200m2; and the hall, room in addition to set outside the window and to direct connection and safe exit evacuation walk outside, should not be opened the other door and window openings;
In 3 a hall, the evacuation chamber for export shall not be less than two, when a hall, room for the construction area of less than 50m2, can be set to an evacuation exit;
4 should be set to automatic fire alarm systems and automatic sprinkler fire extinguishing system;
5 should be set against, exhaust facility.
2.0.4 song and dance entertainment should not be contiguous or in the setting of heritage buildings and museums, library building, should not be contiguous fire hazard for the A, B of the warehouse, should not be in the residential building alterations of song and dance entertainment.
2.0.5 song and dance entertainment should not set in the boiler room ( including direct fired absorption chiller-heater room), fuel oil immersed power transformer chamber, gas regulating station, generator room on a layer, a layer of or near.
2.0.6 song and dance entertainment should not laying gas pipeline and a, B, C liquid pipeline.
2.0.7 is equipped with automatic fire alarm system and linked control automatic sprinkler system or mechanical smoke exhaust system, fire safety facilities such as song and dance entertainment, should according to" code for design of automatic fire alarm" requirements set the fire control room.
2.0.8 song and dance entertainment and other building adjoin or attached to other buildings, should be in accordance with the independent fireproofing subarea. And other places shall be applied between refractory limit of not less than 2.00h non burning body wall and fire resistance limit of not less than 1.00h non burning body is separated from the floor. When the wall must open the door should be set to not less than B the fire door.
2.0.9 song and dance entertainment evacuation walkways on both sides of the partition wall should be made of refractory limit of not less than 1.00h unfired body, room partition should use the fire resistance limit of not less than 0.50h non burning body, the roof load component should be used to limit of fire resistance of not less than 1.00h non burning body.
2.0.10 song and dance entertainment wall should be built to beam plate bottom, not a gap. Pipeline crossing wall, floor space should be noncombustible material packing density.
2.0.11 song and dance entertainment room should open the opening area of not less than the room floor area 2% and not less than 0.48m2 of windows, windows in the short edge length should not be less than 0.9m, and in addition to the curtains, not applied to other materials shielding.
2.0.12 song and dance entertainment venues located in the basement of the rooms will be outside the window open to have the natural lighting and natural ventilation conditions of the window well, windowing requirements shall be according to the standard of 2.0.11 implementation.
2.0.13 song and dance entertainment room should not be set in the sides and ends of pocket corridor. When the door of the room must be set in the evacuation passage is connected with the bag-shaped short walkways, should meet the following requirements:
1 door short walkway entrance from the evacuation distance shall be not more than 5m;
Room 2 of the total building area shall not be greater than 75m2.
3 safety evacuation
3.0.1 song and dance entertainment evacuation exit and evacuation distance number shall conform to the state technical standards on fire control requirements, and exit amount shall not be less than 2, when the construction area of not more than 50m2, can be set to 1 evacuation exit.
3.0.2 song and dance entertainment evacuation passages and exits the net width of not less than 1.40M, its evacuation width, in addition to the state technical standards on fire control provisions, shall be in accordance with its members passed by not less than 1.0m / 100 calculation.
3.0.3 is located in commercial or residential building containing the song and dance entertainment and residential parts of the safety exit should be completely separated set. Both buildings set to meet the 5 / m2 total number of evacuation needed open air evacuation platform through outdoor floor staircase with song and dance entertainment staircases.
3.0.4 is building an underground layer of song and dance entertainment safety exit should be through outdoor.
3.0.5 song and dance entertainment evacuation numbers should be according to the site of the construction area of 0.5 / m2 computing.
3.0.6 song and dance entertainment evacuation stairway to rely on external wall, and should direct the natural lighting and natural ventilation, when not natural lighting and natural ventilation, the addition of positive pressure ventilation facilities. Enclosed staircase door should be used in class B fire door.
3.0.7 exit or evacuation exit should be in accordance with the principle of two-way evacuation dispersed arrangement, 2 adjacent the exit or exit the horizontal distance between the nearest edge shall not be less than 5.0m.
3.0.8 song and dance entertainment evacuation channels should not with less than 3 class time, safety exit should not set the threshold, near the door 1.40M should not set time.
3.0.9 song and dance entertainment to the direction of evacuation evacuation door open, not using the rolling shutter door, revolving door, door hanger and lateral sliding door, the door should not set effect on evacuation mirror decoration and cover.
3.0.10 song and dance entertainment should not be in the evacuation aisle, staircases, exit and exit setup barriers, should not be in the windows installation of fire safety evacuation and rescue fixed guardrail.
3.0.11 song and dance entertainment in business or use period shall ensure that evacuation channels and safe smooth export, with the evacuation door lock should be guaranteed in case of fire, without using a key or other tools can be opened from the inside to the direction of evacuation, opening force should not be greater than 130N.
3.0.12 song and dance entertainment set of normally open fire doors should have fire automatic shut-off function; the normally closed fire doors shall be posted a normally closed fire doors should be kept in a closed state warning language; compartment evacuation behind the door should be posted to the customer the evacuation passage, safety exit position and safety evacuation route safety evacuation schematic diagram
|